BuildCalc

Insulation R-Value by Climate Zone (IECC 2021)

Minimum R-values for new construction per 2021 IRC N1102.1.2. Values shown are the prescriptive path — the simplest option, not the only one. More insulation always outperforms the minimum.

ci = continuous insulation (exterior foam board or similar). If you're unsure of your zone, look it up at energycodes.gov. Most of the continental US falls in Zones 3–6.

ZoneCeiling (attic)Wall cavityFloorBasement wall
Zone 1R-30R-13R-13R-0
Zone 2R-38R-13R-13R-0
Zone 3R-38R-20 or R-13+5ciR-19R-5ci or R-13
Zone 4R-49R-20 or R-13+5ciR-19R-10ci or R-13+5ci
Zone 5R-49R-20+5ci or R-13+10ciR-30R-15ci or R-19+5ci
Zone 6R-49R-20+5ci or R-13+10ciR-30R-15ci or R-19+5ci
Zone 7R-49R-21+12ci or R-13+15ciR-38R-15ci+R-4 or R-19+8ci
Zone 8R-49R-21+16ciR-38R-15ci+R-4

Important notes

  • • Values are minimums for the prescriptive path — performance and U-factor paths may differ.
  • • Local code amendments can require higher R-values. Always verify with your local building department.
  • • Existing homes doing energy upgrades may qualify for exceptions — check your local adopted code edition.
  • • Vapor retarder class requirements depend on climate zone and assembly type.

Related calculators